Welcome to Anhui Xin Huan Neng Electrical Co., LTD.
    RSS | Site map|disclaimer|中文版
Anhui  Xin Huan Neng Electrical Co., LTD.
freephone

0550-7989777

Popular Keywords:
联系我们
    全国咨询热线:0550-7989777
  • Mobile:18019898888
  • Email:xhn@ahxhn.cn
  • Address:69, second road, Tianchang economic development zone, Anhui province
Intelligent power monitor
zhi-neng-dian-li-jian-ce-yi
Several kinds of intelligent electric power monitor and cont
Browse:
Add Time: 2016-08-18 17:22:58
Recommendation:
Several kinds of intelligent electric power monitor and cont的产品详细介绍:

A, product function and characteristics of the contrast:

function model

  YW2000

  YW2000A

  YW2010

  YW2100

In both Chinese and English display window

There are

There is no

There is no

There are

Automatic steady zero

There are

There are

There are

There are

Digital setting

There are

There are

There are

There are

Power lost memory

There are

There are

There are

There are

The ability to resist electromagnetic interference

strong

strong

strong

strong

Analog input

There is no

There is no

There is no

There are

Many kinds of connection mode

There are

There are

There are

There are

The automatic fault diagnosis

There are

There are

There are

There are

Programmable state setting

There are

There are

There are

There are

Three remote and automatic control

There is no

There is no

There is no

There are

Accuracy of measurement

high

high

higher

higher

installation

Surface mounting

Guide rail, screw,

Guide rail, screw,

Surface mounting

Second, the main general technical indicators

1, measuring line system and power

Can measure a three phase four wire circuits, or any other type of all phase voltage/line voltage (V), current (I), power (P, Q, S) electrical energy (Wh, Qh), power factor (PF), frequency (F) and zero sequence current (I0) 34 parameters.

2, working voltage:

AC85 ~ 40 ~ 70 hz, 265 v DC85 ~ 330 v (standard)

DC18 ~ 90 v (optional)

3, the machine power consumption: 4 or less VA

4, overload ability:

Voltage: 750 v continuous;1000 v to 10 seconds;1200 v 3 seconds

Current: 2 times rated continuous;

20 times rated 1 seconds;

5, input range:

U: 5 ~ 120 V / 600 V (Max 600 V), automatic switch range

I: 0 ~ 1 A / 5 A, 6 A), automatic switch range

6, absorption power consumption:

Voltage: < 0.8 VA / 400 v, < 0.25 VA / 220 v

Current: < 0.1 VA / 5 a

7, accuracy:


parameter model

  YW2000

   YW2000A

  YW2010

  YW2100

Voltage VX

0.2%RD~0.5%RD

0.2%RD~0.5%RD

0.2%RD~0.5%RD

0.2%RD

Current I in Xx

Active power P

0.5%RD

0.5%RD

0.5%RD

0.5%RD

Reactive power Q

0.5%RD

0.5%RD

0.5%RD

0.5%RD

Apparent power S

0.5%RD

0.5%RD

0.5%RD

0.5%RD

Power factor PF

0.5%RG

0.5%RG

0.5%RG

0.5%RG

Active power Wh

0.5%RD

0.5%RD

0.5%RD

0.5%RD

Reactive power Qh

1.0%RD

1.0%RD

1.0%RD

0.5%RD

I0 zero sequence current

5%RG

5%RG

1%RG

0.2%RG

Hz frequency

0.1%RG

0.1%RG

0.2%RG

0.2%RG

8, programmable design.

Programming mode: (password)

Measurement system of three phase four wire/three-phase three-wire/phase 2 line / / three-phase equilibrium phase three line

CT, PT variable ratio: 1 ~ 59999

Page display content: in the time/picture (YW2000, YW2100 only)

Communications:

Baud rate:

1200/2400/4800/9600 (only YW2000, YW2000A, YW2010)

300/600/1200/2400/1200/2400/19200 (YW2100 only)

Data bits: 8, or 7

Check digit: odd/even/no parity bit

Stop bits: 1 or 2

Address: 1 ~ 255, 1 ~ 255 (YD2100 only)

Communication agreement: the Modbus RTU/Modbus ASCII RS - 485 / RS232C, at the same time can only use one of them

The clock: year, month, day, hours, minutes, seconds, week

The clock error: 0.5 seconds / 24 hours

Electrical energy accumulation reset: (password)

Calibration: (password)

9, dielectric strength

Object: between the input/output/power supply

Reference: IEC688-1992

Leakage current test methods: AC2KV 1 minute 2 ma

10, electromagnetic compatibility

Surge (1.2/50-8/20 us)

Object: power supply, I/O line

Reference: IEC61000-4-5 / IEC61000-4-11

Test method: 4 kv (1.2 x 50 us)

Transient pulse sequence

Object: power supply, I/O line

Reference: IEC61000-4-4

Test method: power supply: 4 kv 2.5 KHz

The I/O lines: 2 kv 5 KHZ

Electrostatic discharge

Object: power supply, I/O line

Reference: IEC61000-4-2

Contact discharge: 6 kv

The air gap discharge: 8 kv

Radio frequency (rf) electromagnetic fields

Object: the device ontology

Reference: IEC61000-4-3

Test method: 10 v/m medium intensity of electromagnetic radiation (such as the distance of not less than 1 meter of the portable radio)

The stability of

Temperature range: 10 ~ + 50 ℃

Temperature: 100 PPM / ℃

Long term stability: < 0.2% per year

11, isolation:

Mutual isolation between the input/output/power

Three, on-off input (remote communication)/output (remote control) (YW2100)

Switch input:

All empty contact input

(remote communication) : 50 ms response time

Switch output:

Three road relay output

Normally open/closed double contact output

Contact load capacity: 5 a long-term electricity.

(remote/control) :

Export delay and return time can be set

Communications set according to conditions of automatic remote control output, or export.

Please specify the type and auxiliary power order

Example: book YW2100 intelligent power measurement and control device, auxiliary power supply: AC220V

General instructions

Structure:

YW2000A and YW2010 for wiring in front of the plate,

After wiring YW2000 and YW2100 for board

Installation method:

YW2000A and YW2010 for guide installation or screws.

YW2000 and YW2100 for surface mounting

Disk hole size:

YW2000 is: 92 mm * 92 mm

YW2100 is: 177 mm * 127 mm

Shell material:

Flame retardant plastics (all black)


Return To The Top