A: the product features and use: This product is suitable for AC rated voltage 0.6/1KV and below power transmission line for fixed wiring or mobile electrical connecting cables, products with heat radiation, cold resistant, acid and alkali and corrosive gases and waterproof properties, soft cable structure, convenient radiation, high temperature and stable electrical performance environment (Gao Han) under the anti aging performance is outstanding, long service life, widely used in metallurgy, electric power, motor wiring, petrochemical, electronics, automobile manufacturing and other industries.
Two: product implementation standards
Q/HHTZH001.1
Flame retardant performance test implementation GB12666-90 requirements
Three: use characteristics
1 AC rated voltage: U0/U 0.6/1KV
Maximum operating temperature: 180
Minimum ambient temperature: fixed -60
2 cable installation temperature should not be less than -25.
3 cable allowable bending radius: the cable is 10 times of the cable diameter
Four: basic model and name
Table 1
Model
Product name
KGG copper core silicone rubber insulation sheath control cable
KGGP copper core silicone rubber insulation sheath braided shielding control cable
KGG22 copper core insulated silicon rubber sheathed control cable
KGGR copper core silicon rubber insulated silicon rubber sheath control flexible cable
KGG32 copper core insulated silicon rubber sheathed fine steel wire armoured control cable
YGC
Silicon rubber insulated silicon rubber sheathed power cable
YGCR
Power soft cable for silicon rubber insulated silicon rubber sheath
YGCP
Silicon rubber insulated silicon rubber sheathed copper braid shielded power cable
YGC22
Silicon rubber insulated and sheathed power cable
JGG
Silicone rubber insulated silicone rubber sheath mounting line
JGGR
With the installation of flexible silicon rubber insulation and sheath of mobile
JGGP
Silicon rubber insulation, silicon rubber sheath, copper braided shielding installation line
JHXG
Silicon rubber insulation motor wiring
Note: flame retardant silicone rubber cable type ZR copper conductor wire core can be used in tin.
Five: code name and meaning
Table 2
Code
Code meaning
Y
Series code (mobile flexible cable)
G
silicon rubber
C
Heavy
Twenty-two
Steel tape
P
Copper braid shield
R
Stranded conductors
J
Motor wiring
Six: the main technical indicators
1 finished cable conductor (class R) DC resistance (in accordance with the provisions of GB3956) refer to appendix A Table 1 and table 2.
2.20 the insulation resistance shall not be less than 100MΩ /KM
3 finished cable withstand AC 50HZ3.5KV/5min voltage test without breakdown.