Browse: | |
---|---|
Add Time: | 2016-08-20 17:11:57 |
Recommendation: |
Cross-linked power cable的产品详细介绍:
Product description: |
This product by GB1270 the rated voltage up to and including 35 kv plastic insulated power cable, copper, aluminum core standard production, at the same time can also be based on user needs according to the international standard of IEC, English, German and American standard production. |
YJV | YJLV | YJY | YJLY |
YJV22 | YJLV22 | YJV23 | YJLV23 |
YJV23 | YJLV23 | YJV33 | YJLV32 |
YJLV33 |
This product is suitable for rated power-frequency voltage up to 3.6/26/35 kV - kV distribution circuit for distribution power.
Using features:
Low rated power-frequency voltage up to Uo/U for 3.6/6 kv - including 26/35 kv.
Low cable conductors allow long the highest working temperature is 90 ℃.
Low short circuit (the longest duration of no more than 5 s) cable conductor of the highest temperature does not exceed 250 ℃.
Low when the ambient temperature under installation should not below 0 ℃.
When the bending radius: three core cable should not less than 15 times the cable diameter;Single core cable should not less than 20 times the cable diameter.
Cable of rated voltage
When the rated voltage of the cable shall be suitable for the operation condition of the cable system, using Uo/U (Um) KV said.
Uo - from the conductor to ground or metal shielding cable design between the rated power frequency voltage;
U - cable design with rated power frequency voltage between conductors;
Um - equipment can withstand a maximum of the "highest system voltage".
On A:Power cable
Next:General rubber set soft cable