Product description:
An overview of the
WZ series industrial heat resistance as temperature measurement sensor, usually with temperature transmitter, controller and display instrument, process control system, to directly measure or control in the production of various - 200 ℃ to 500 ℃ within the scope of the liquid, steam and gas medium, as well as the temperature of the solid surface.
Thermal resistance is the use of the material when the temperature changes itself along with the change of resistance and characteristics to measure temperature. When the temperature of the measured medium body with the tonsure, measured the temperature of the temperature sensing element is the average temperature range of the medium.
Despite the appearance of various thermal resistance difference is very big, but they are roughly similar, the basic structure of the general temperature inductive element, insulation casing, protection tube, and junction box and other major parts
The characteristics of
Reed, pressure temperature sensing element, ant-vibration performance is good.
, temperature measurement precision is high;
High mechanical strength, good compression performance;
Imported film resistance element, reliable and steady performance.
The working principle of
Thermal resistance is the use of the material when the temperature changes, its resistance also along with the change of characteristics to measure temperature.When resistance changes, the work shows the temperature resistance of the meter.
The main technical parameters
Product standards
IEC584
IEC1515
GB/T16839-1997
JB/T5582-91
The normal temperature insulation resistance
Thermal resistance at ambient temperature for 15-35 ° C, relative humidity is not more than 80%, test voltage for 10-100 - v (dc) electrode and outer casing of the insulation resistance between > 100 m omega.
Measuring temperature and tolerance
Type no. | Degree, | Temperature measurement range | Precision grade | Margin of error |
WZC | Cu50 Cu100 | + 100-50 - | -- -- -- | Plus or minus(0.30+0.005) ltl |
WZP | Pt100 | - 200 - + 500 | Alevel | Plus or minus(0.15+0.002) ltl |
Blevel | Plus or minus(0.30+0.005) ltl | |||
TWZKP | Pt100 | - 200 - + 500 | Alevel | Plus or minus(0.15+0.002) ltl |
Blevel | Plus or minus(0.30+0.005) ltl | |||
TWZKPEXB | Pt100 | - 200 - + 500 | Alevel | Plus or minus(0.15+0.002) ltl |
Blevel | Plus or minus(0.30+0.005) ltl |