Product description:
I. overview
Alternating current (voltage) is a transmitter can be measured AC current (voltage) into the instrument according to the linear ratio of the output DC voltage or DC current, widely used in electric power, telecommunications, petroleum, coal, metallurgy, railway, municipal and other departments of the electrical device, automatic control and scheduling system.
AC current and voltage transmitter have single -, three - way combined structure:
1, high accuracy (typical: 0.2% best 0.05%).
2, the entire range has a very high linearity.
3, a high degree of integration, simple structure, excellent temperature characteristics and long-term stability of the work, so that the transmitter from the regular calibration.
Two, product name and model
Name type auxiliary power single AC current transducer YWD-I, YWE-I, YWF-I, YWL-IYWD AC:220V 110VDC:220V 110V 48V series optional: 24VYWE, YWF, YWL, 15V, DC:24V series of optional: 12V three YWD-3I, YWE-3I combination of AC current transducer, YWL-3I single AC voltage transducer YWD-U, YWE-U, YWF-U, YWL-U three YWD-3U, YWE-3U combination of AC voltage transmitter YWL-3U
Three, the implementation of standards
GB/T13850-1998idtIEC688:1992
Four, the main technical indicators
A) accuracy level: level 0.2, level 0.5
B) input, output and auxiliary power parameters
Vn input voltage V00 ~ 70VV10 ~ 120VV20 ~ 250VV30 ~ 300VV40 ~ 450VV50 ~ 500VV6 custom An input current A10 ~ 1AA20 ~ 5AA30 ~ 10AA40 ~ 30AA50 ~ 50A note: A4, A5, A6, A7, A8 is only suitable for YWF class structure products. A60 ~ 75AA70 ~ 100AA80 ~ 150AA9 user defined Pn power supply P1DC24V± 15%P2DC12V± 15%P3AC220V± 15%P4 user custom On output from O10 ~ 5VO21 ~ 5VO30 ~ 2OmAO44 ~ 20mAO5 custom user
C) input frequency: 50Hz± 5Hz
D) overload input: current: 2 times continuous for 30 second
Voltage: 2 times continuous
E) absorption power: voltage loop: 0 5VA/450V
Voltage loop: 0.2VA/100V
Current loop: 0.1 VA/5A
F) response time: ≤ 350ms
G) output load: current: when auxiliary power supply ≥ 24V, RL≤ 650Ω;
When the auxiliary power supply for 12V, 15V, RL≤ 300Ω;
Voltage: RL≥ 2kΩ
H) power frequency withstand voltage: input / output / enclosure: AC 2kV/min
I) insulation resistance: ≥ 20MΩ
J) impulse voltage: 5kV/1.2-50μ s (peak)
K) working environment: temperature: -10 to 50 degrees Celsius humidity: 10 ~ 90% (no condensation)
L) storage conditions: temperature: -40 to 70 degrees Celsius humidity: 10 ~ 95% (no condensation)
(m) outline dimensions:
YWD-I, YWD-U: 55 mm× 75 mm× 120mm³
YWD-3I, YWD-3U: 110 mm× 75 mm× 120mm
YWE-I, YWE-U: 42mm× 75 mm× 70mm
YWE-3I, YWE-3U: 110 mm× 75 mm× 70mm
YWF-I, YWF-3U: 104 mm× 31 mm× 77mm
YWL-I (3I), YWL-U (3U): 75 mm× 22.5mm× 100mm