1, use: This product is suitable for AC rated voltage 450/750V and below the power plant fixed installation.
2, product standards: GB5023, 2-85 rated voltage 450/750V and below PVC insulated cable (wire) fixed laying cable (wire)
3, product characteristics: 1) rated voltage U0/U is divided into 450/750V and 300/500V. 2 long term allowable working temperature of cable: BV-105 type … … shall not exceed 105 DEG C; other models … … shall not exceed 70 degrees C. 3) installation temperature should not lower than 0 DEG C; 4) cable bending radius: cable diameter less than 25mm (D) … … should be not less than 4D; the cable diameter (D) of 25mm and above … … should not be less than 6D
4, cable type, name and scope of use
Model
Name
Use scope
BV copper core PVC insulated cable (wire)
BLV aluminium core PVC insulated cable (wire)
BVR copper core PVC insulated cables (wires) (wire) are required for flexible installation
BVV copper core PVC insulated and sheathed round cable (wire) fixed
BLVV al core PVC insulated PVC sheathed round cable PVC (wire) fixed
BVVB copper core PVC insulated PVC sheathed flat cable (wire) (wire) fixed installation
BLVVB al core PVC insulated PVC sheathed flat cable (wire) (wire) fixed installation
BV-105 copper core 105 degree PVC insulated wire
5, production range
Model
Rated voltage V (V)
Core number
Nominal cross-section
BV 300/500 1 0.5-1
450/750 1 1.5-300
BLV 450/750 1 2.5-300
BVR 450/750 1 2.5-70
BVV 300/500 2, 3, 4, 5 1.5-35
BLVV 300-500 1 2.5-10
BVVB 300-500 2, 3 0.75-10
BLVVB 300/500 2, 3 2.5-10
BV-105 450/750 1 0.5-6