Intelligent power monitor
zhi-neng-dian-li-jian-ce-yi
SWP - LCD - PID self-tuning controller
Browse:
Add Time: 2016-08-22 15:31:54
Recommendation:
SWP - LCD - PID self-tuning controller的产品详细介绍:

Product description:

SWP - LCD series PID self-tuning control instrument is suitable for the need for high accuracy measurement control system.
SWP - LCD series PID self-tuning controller integrating digital instrument and analog meter, for velocity, temperature, pressure, liquid level measurement signal is digital display control, make the measured value shows more clear and intuitive.
One, the main characteristics
1, respectively with PID control output and analog output all the way, all the way to apply various measurement control occasions.
2, hand/auto undisturbed switching, since the state can modify the parameters.
3, has a variety of modes of adjusting output (PWM output, the output controllable trigger rules, solid state relay output and voltage/current output).
Second, the special technical parameters
The output is controlledPWM output, thyristor trigger output, solid state relay output, the output voltage/currentTo set/display precision+ 0.5% FS + 1 digit Max.Settings and display values match, no relative errorscale0.0% - 100.0% (unit: 0.1%)Integral (reset) time0-9999 - s (unit: 1 s)Differential (ratio) of time0-9999 - s (unit: 1 s)Control cycle1, 2, 4, 6, 15, 30, 60, 120, 240 s (unit: 1 s)Sampling period0.5s
Three, instrument appearance and wiring diagram (hereinafter as the basic wiring way, special order please see random wiring diagram)
Instrument size: 80 * 160 * 140 mm
Hole size: 76 x 152 mm
Weight: 400 g
Four, SWP - LCD series PID parameters self-tuning controller spectrum chart
Type no.codeSaid MingSWP-LCD-N□ □ □□ -□ □ -□ □□ -□ □-□-□A new generation of PID self-tuning controllerShape featuresDSHorizontal type display instrumentVertical display instrumentOverall dimensions8160 x 80 mm (horizontal type), 160 (vertical) x 160 mmControl action05PID self-tuning controlCommunication methods02489There is no communicationCommunication interface of RS - 232 cCommunication interface of RS - 422Communication interface of RS - 485The communication interface of special specificationsControl the output-See "control output way"Analog output-See "analog output way"Input typetwentySee "input type"The first alarm wayNHLNo alarm (can be omitted)Upper limit alarmThe lower limit alarmThe second alarm way-See the "alarm mode"Feed outputPDC24V feed outputThe power supply modeWT  DC24V power supplyAC90 ~ 265 v power supply, switching power supply)AC220V power supply, linear power supply, can be omitted)
Taken the input type:
codeInput typeMeasuring rangecodeInput typeMeasuring rangecodeInput typeMeasuring range01B400 ~ 1800 ℃09Pt100.199.9 ~ 199.9 ℃1730 ~ 350 omega.-1999~99999 d02S0 ~ 1600 ℃10Cu5050.0 ~ 150.0 ℃18Special specificationsA specific user03K0 ~ 1300 ℃11Cu10050.0 ~ 150.0 ℃194 ~ 20 mA prescribing-1999~99999 d04E0 ~ 1000 ℃124~20 mA-1999~99999 d200 ~ 10 ma, prescribing-1999~99999 d05T- 200 ~ 400 ℃130~10 mA-1999~99999 d211 ~ 5 V prescribing-1999~99999 d06J0 ~ 1200 ℃141~5 V-1999~99999 d220 ~ 5 V prescribing-1999~99999 d07Wre0 ~ 2300 ℃150~5 V-1999~99999 d23Switch inputSee the table below08Pt100- 200 ~ 650 ℃160~20 mA-1999~99999 d
U all need to set up the parameter meter secondary switch input, can switch input multiple points, can input index number is as follows:
codeInput typecodeInput typecodeInput typecodeInput typecodeInput type01B05T09Pt100.1141~5 V211 ~ 5 V prescribing02S06J10Cu50150~5 V220 ~ 5 V prescribing03K07WRe124~20 mA194 ~ 20 mA prescribing  04E08Pt100130~10 mA200 ~ 10 ma, prescribing
Note: the same degree, and instrument selection code programming code is different, please pay attention to in the instrument Settings.
u Analog output
Selection of the code012345Output wayThere is no outputrelay4~20mA0~10mA1~5V0~5V
u Alarm output way
Selection of the codeNHLGADOutput wayNo alarm (can be omitted)Upper limit alarmThe lower limit alarmWithin the deviation report to the policeOutside the deviation report to the policeThe LBA alarm
U type, for example:
SWP-LCD-ND805-21-08-HL-P-W
PID self-tuning controller, RS - 232 communication mode, the output relay output, input types as Pt100, the first alarm for upper limit alarm, the second alarm
As the lower limit alarm, feed output, DC24V power supply, horizontal table.
Second, the special technical parameters
The output is controlledPWM output, thyristor trigger output, solid state relay output, the output voltage/currentTo set/display precision+ 0.5% FS + 1 digit Max.Settings and display values match, no relative errorscale0.0% - 100.0% (unit: 0.1%)Integral (reset) time0-9999 - s (unit: 1 s)Differential (ratio) of time0-9999 - s (unit: 1 s)Control cycle1-250 - s (unit: 1 s)Sampling period0.5s
Three, instrument appearance and wiring diagram (please refer to the following as the basic wiring, special order random wiring diagram)
modelSWP - LCD - NP series (swing)The wiring diagramInstrument appearanceInstrument size: 160 * 80 * 140 mmHole size: 152 x 76 mmWeight: 400 g
Four, SWP - - NP series LCD 32 PID programmable controller spectrum chart
A new generation of large screen with backlit LCD display instrument
u Input type
codeInput typeMeasuring rangecodeInput typeMeasuring rangecodeInput typeMeasuring range01B400 ~ 1800 ℃09Pt100.199.9 ~ 199.9 ℃1730 ~ 350 omega.-1999~99999 d02S0 ~ 1600 ℃10Cu5050.0 ~ 150.0 ℃18Special specificationsA specific user03K0 ~ 1300 ℃11Cu10050.0 ~ 150.0 ℃194 ~ 20 mA prescribing-1999~99999 d04E0 ~ 1000 ℃124~20 mA-1999~99999 d200 ~ 10 ma, prescribing-1999~99999 d05T- 200 ~ 400 ℃130~10 mA-1999~99999 d211 ~ 5 V prescribing-1999~99999 d06J0 ~ 1200 ℃141~5 V-1999~99999 d220 ~ 5 V prescribing-1999~99999 d07Wre0 ~ 2300 ℃150~5 V-1999~99999 d23All switch inputSee the table below08Pt100- 200 ~ 650 ℃160~20 mA-1999~99999 d24Frequency of the input0~10KHz 
u Switch the input just set up the parameter meter secondary to switch input multiple points, can input index number is as follows:
codeInput typecodeInput typecodeInput typecodeInput typecodeInput type01B05T09Pt100.1141~5 V211 ~ 5 V prescribing02S06J10Cu50150~5 V220 ~ 5 V prescribing03K07WRe124~20 mA194 ~ 20 mA prescribing  04E08Pt100130~10 mA200 ~ 10 ma, prescribing
Taken the alarm output
Selection of the codeNHLGADOutput wayNo alarm (can be omitted)Upper limit alarmThe lower limit alarmWithin the deviation report to the policeOutside the deviation report to the policeThe LBA alarm
Taken the analog output
Selection of the code012345Output wayThere is no outputrelay4~20mA0~10mA1~5V0~5V
u Communication methods
Selection of the code02489Communication methodsThere is no communicationRS-232RS-422RS-485Special specifications
Taken the control output
Selection of the code0123456789Output wayThere is no outputrelay4~20mA0~10mA1~5V0~5VSCR outputSSR outputSpecial specificationsSOT output
SCR, thyristor zero trigger pulse output, SSR, solid-state relay control output, SOT - bidirectional thyristor output
U type, for example:
①SWP-LCD-NP805-21-09-HL-P-W-S
For RS - 232 communication mode, output relay output, input types for Pt100.1, first alarm for the upper limit alarm, the alarm for the lower limit alarm, DC24V feed output, DC24V power supply, set table.
②SWP-LCD-NP805-81-08-LH-P-T
For RS - 485 communication mode, output relay output, input type of Pt100, first alarm for the lower limit alarm, the second alarm for upper limit alarm, DC24V feed output, AC90 ~ 265 v power supply, switching power supply)